Unic electric is a source of learning electrical video for Electrician, Technician, Site engineers and also for college going students.
unic electric channel देखने से आपको यह फायदा होगा
Building और industries में जो भी इलैक्टिकल डिवाइस यूज होता है
उसका working fuction, Control and power wiring देखने और समझने को मिलेग !
हम unic electric channel पर सप्ताह में 2 विडियो अपलोड करते हैं सोमवार और गुरुवार को
यहां पर आपको Single phase switch board wiring, fan and balb connection
और three phase panel's power and control wiring ,
HT Panel, LT Panel, APFC Panels, Motor connection,
starter's power and control wiring, cables sizing and cable selection,
MCB size selection, all type mcb, breakers sizing and selection,
ACB, VCB, And about Transformer, Transformer's protections,
Earthing , इत्यादि से Related विडियो देखने को मिलेगा !
If you are interested in this channel make sure to subscribe and click the bell icon
so you never miss my video.
Also follow on
Instagram
Facebook
Unic Electric
⚡ Understanding 7 Main Types of Electrical Panels
🔌 1️⃣ PCC Panel (Power Control Center)
Purpose:Controls and distributes main incoming power from the transformer.
Key Features:
1:-Equipped with ACBs, MCCBs, relays, and metering devices
2:-Provides overload and short-circuit protection
3:-Supplies power to MCC panels and sub-panels
Used In:Large industries, process plants, utility substations
💡2️⃣ MCC Panel (Motor Control Center)
Purpose:Controls and protects motors across different process areas.
Key Features:
1:-Includes contactors, overload relays, MCBs, and push buttons
2:-Enables local and remote operation
3:-Simplifies maintenance and troubleshooting
Used In:Water plants, chemical plants, conveyors, and HVAC system
⚙️ 3️⃣ APFC Panel (Automatic Power Factor Control)
Purpose:Maintains power factor near unity and reduces electricity penalties.
Key Features:
1:-Contains capacitor banks and APFC relays
2:-Automatically switches capacitors ON/OFF based on load
3:-Reduces reactive power lossand improves system efficiency
Used In:Factories, commercial buildings, and plants with high inductive load
🔄 4️⃣ VFD Panel (Variable Frequency Drive)
Purpose:-Controls motor speed and torque by varying frequency and voltage.
Key Features:
1:-Enables soft starting and smooth acceleration
2:-Saves energy during partial load conditions
3:-Reduces mechanical wear and noise
Used In:Pumps, fans, compressors, blowers, and HVAC systems
🧠5️⃣ PLC Panel (Programmable Logic Controller)
Purpose:-Provides automation and process control using logic-based programming.
Key Features:
1:-Receives signals from sensors and transmitters
2:-Executes logic to control actuators, motors, solenoids
3:-Enhances precision, safety, and productivity
Used In:Process industries, bottling plants, and assembly lines
🚨 6️⃣ Control Panel (Process Control & Monitoring)
Purpose:- Serves as the
interface between operator and system.
Key Features:
1:- Contains switches, indicators, meters, and HMI displays
2:- Enables manual and automatic operation
3:-Helps in monitoring system performance.
Used In:- Boilers, compressors, packaging and batching plants
🔋 7️⃣ Distribution Panel (Sub Power Distribution)
Purpose:- Safely distributes power to various sub-loads or areas.
Key Features:
1:- Uses MCBs, ELCBs, and isolators for protection
2:-Divides load into circuits for safety and convenience
3:-Ensures balanced load and fault isolation
Used In:-Offices, workshops, residential and industrial buildings
🖐️🖐️🖐️
*YOUTUBE*:-lnkd.in/e4pj_G54
🔖 **#ElectricalEngineering #ElectricalPanels #PCCPanel #MCCPanel #APFCPanel #VFDPanel #PLCPanels #ElectricalMaintenance #PowerDistribution #IndustrialAutomation #EngineeringKnowledge #ElectricalProjects
2 months ago | [YT] | 3
View 0 replies
Unic Electric
🔹 Transformer Testing – Explanation & Procedure
1.Insulation Resistance (IR) Test
Purpose:
To check the insulation strength between windings to windings and winding & earth.
Ensures no moisture or deterioration.
Procedure:
Use Megger (500V / 1000V / 2500V / 5000V as per rating).
Disconnect all connections from transformer bushings.
Apply DC voltage between:
* HV ↔ LV
* HV ↔ Earth
* LV ↔ Earth
Record insulation resistance values in MΩ.
For better check, also calculate Polarization Index (PI = IR at 10 min / IR at 1 min)
2.Winding Resistance Test
Purpose:
To measure winding resistance of LV and HV windings.
Detects loose connections, shorted turns, or high-resistance joints.
Procedure:
Use a DC resistance test kit (Micro-ohmmeter)
Connect across each winding terminal (HV side & LV side).
Pass DC current and measure resistance.
Compare with design/previous values; should be balanced across phases.
3.Magnetic Balance Test
Purpose:
To detect inter-turn short circuits in three-phase transformers.
Ensures magnetic circuit balance of windings.
Procedure:
Apply low voltage AC (around 230V single phase supply) between two phases of HV winding at a time.
Measure voltages induced in the third phase.
Normal condition → induced voltages follow a definite balanced pattern.
Abnormal imbalance → indicates possible winding fault.
4.Vector Group Test
Purpose:
To confirm the vector group (phase displacement) of transformer windings.
Ensures parallel operation compatibility.
Procedure:
Apply 3-phase supply to HV side.
Measure phase-to-phase and phase-to-neutral voltages on HV & LV.
Compare phase displacement between HV and LV voltages.
Verify with nameplate vector group (e.g., Dyn11, YNd1, etc.).
5.Voltage Ratio Test
Purpose:
To verify that the ratio of primary to secondary voltages matches the design.
Procedure:
Apply rated voltage on HV side (or a reduced test voltage).
Measure voltage on LV side.
Calculate ratio: HV / LV.
Compare with nameplate ratio (tolerance ±0.5%).
6.Turns Ratio (TTR) Test
Purpose:
To accurately check the number of turns ratio between HV and LV.
More precise than simple voltage ratio test.
PROCEDURE:
Use TTR meter(special kit).
Connect across HV and LV windings.
Inject a low test voltage from TTR kit.
Instrument directly displays turns ratio & phase angle error.
Compare with rated ratio.
3 months ago | [YT] | 2
View 0 replies
Unic Electric
🔹 Transformer Testing – Explanation & Procedure
1.Insulation Resistance (IR) Test
Purpose:
To check the insulation strength between windings to windings and winding & earth.
Ensures no moisture or deterioration.
Procedure:
Use Megger (500V / 1000V / 2500V / 5000V as per rating).
Disconnect all connections from transformer bushings.
Apply DC voltage between:
* HV ↔ LV
* HV ↔ Earth
* LV ↔ Earth
Record insulation resistance values in MΩ.
For better check, also calculate Polarization Index (PI = IR at 10 min / IR at 1 min)
2.Winding Resistance Test
Purpose:
To measure winding resistance of LV and HV windings.
Detects loose connections, shorted turns, or high-resistance joints.
Procedure:
Use a DC resistance test kit (Micro-ohmmeter)
Connect across each winding terminal (HV side & LV side).
Pass DC current and measure resistance.
Compare with design/previous values; should be balanced across phases.
3.Magnetic Balance Test
Purpose:
To detect inter-turn short circuits in three-phase transformers.
Ensures magnetic circuit balance of windings.
Procedure:
Apply low voltage AC (around 230V single phase supply) between two phases of HV winding at a time.
Measure voltages induced in the third phase.
Normal condition → induced voltages follow a definite balanced pattern.
Abnormal imbalance → indicates possible winding fault.
4.Vector Group Test
Purpose:
To confirm the vector group (phase displacement) of transformer windings.
Ensures parallel operation compatibility.
Procedure:
Apply 3-phase supply to HV side.
Measure phase-to-phase and phase-to-neutral voltages on HV & LV.
Compare phase displacement between HV and LV voltages.
Verify with nameplate vector group (e.g., Dyn11, YNd1, etc.).
5.Voltage Ratio Test
Purpose:
To verify that the ratio of primary to secondary voltages matches the design.
Procedure:
Apply rated voltage on HV side (or a reduced test voltage).
Measure voltage on LV side.
Calculate ratio: HV / LV.
Compare with nameplate ratio (tolerance ±0.5%).
6.Turns Ratio (TTR) Test
Purpose:
To accurately check the number of turns ratio between HV and LV.
More precise than simple voltage ratio test.
PROCEDURE:
Use TTR meter(special kit).
Connect across HV and LV windings.
Inject a low test voltage from TTR kit.
Instrument directly displays turns ratio & phase angle error.
Compare with rated ratio.
3 months ago | [YT] | 0
View 0 replies
Unic Electric
https://youtu.be/xKeo8llYbns
☝☝☝Basic Electrical Tools
3 years ago | [YT] | 3
View 0 replies
Unic Electric
ट्रांसफार्मर का न्यूट्रल अर्थिंग क्यों करते हैं
👇👇👇👇👇
https://youtu.be/lMsla6yuycc
3 years ago | [YT] | 3
View 0 replies
Unic Electric
फ्यूज कितने एम्पियर का लगाएं
https://youtu.be/LDVWCSZRBSQ
3 years ago | [YT] | 3
View 0 replies
Unic Electric
How To Select Fuse Rating ???
👇👇🤑🤑
https://youtu.be/opk1xveRE2g
3 years ago | [YT] | 7
View 0 replies
Unic Electric
What's The Cause ????
3 years ago (edited) | [YT] | 5
View 0 replies
Unic Electric
KVA To Amps Calculation
https://youtu.be/ZK-QcinOBoY
3 years ago | [YT] | 1
View 0 replies
Unic Electric
केवल ट्रेक का बैंड कैसे बनाया जाता हैं लिंक पर क्लिक करके देखें
https://youtu.be/a1oulLAFEWY
3 years ago | [YT] | 3
View 0 replies
Load more